BLADE ADJUSTMENT FOR DESIRED
VENTILATOR AIR
The amount of ventilation air supplied by the
commercial room ventilator is dependant on four (4)
factors.
1. Return air duct static pressure drop.
2. Supply air duct static pressure drop.
3. Indoor blower motor speed.
4. Damper blade open position setting.
Refer to the graph below to determine the blade setting
necessary to achieve the ventilation air required for
each operating mode.
FACTORY DEFAULT SETTINGS ARE:
C**H T**H
T**S W**H
Potentiometer R1. 17 17
Potentiometer R2. 14 14
Potentiometer R3. 12 NA
For more accurate adjustment, use a owhood over
the intake opening to measure and adjust the airow
operation.
Potentiometer R1. Adjusts the airow during blower
operation only.
Potentiometer R2. Adjusts the airow during 1st stage
cooling or heating operation.
Potentiometer R3. Adjusts the airow during 2nd
stage cooling or heating operation.
Energize blower only mode and adjust #1
Potentiometer to desired airow.
Energize 1st stage cooling mode and adjust #2
Potentiometer to desired airow.
Energize 2nd stage cooling mode and adjust #3
Potentiometer to desired airow.
Minimum damper position when using CO
2
control
damper should be fully closed at 700 ppm or lower, if
not Potentiometer R7 can be adjusted clockwise (CW)
to close it. If it is fully closed at 700 ppm or lower, no
adjustments required.
GRAPH 1
C36H, C42H & W38H1 VENT AIRFLOW
0
100
200
300
400
500
600
700
0 5 10 15 20
Ventilation Airflow (cfm)
Stage 2
Stage 1
Ventilation