G500i Compact Indoor System
www.conserv.com 93 www.conserv.com
Single-core compact indoor systems contain one C500S high-performance
enthalpy exchange ConsERV™ core, suitable for flows up to 520 CFM. Airflow is
provided by compact and efficient forward-curved blowers with four-speed direct
drive motors.
G500 i -___ -____
G = G series Overall system type
500 Nominal flow rate
i = Indoor Installation location
0 = 4-speed motor
1 = Manual damper
Fan / flow control
1 = 115 V
2 = 208 V or 230 V
4 = 460 V
Electrical voltage
1 = Single phase
3 = Three phase
Electrical service
S = Short side of unit
L = Long side of unit
Outside air intake direction
S = Short side of unit
L = Long side of unit
Supply air exit direction
S = Short side of unit
L = Long side of unit
Return air intake direction
S = Short side of unit
L = Long side of unit
Exhaust air exit direction
G Series Model Number Key
Example: G500i-021-SLSL
This unit has a direct drive blower with four speeds. The power supply is either 208V/1φ or
230V/1φ (there is no difference in the unit delivered from the factory). The intake ducts are
both on the short end of the cabinet, while the blower exits are both located on the long
sides of the unit (see diagrams on next page).
Electrical Information:
The chart to the right lists the nameplate
electrical specifications in amperes.
Electrical Service FLA MCA MOP
115V / 1
φ
8.2 10.3 15
208V / 1
φ
4.2 5.3 15
230V / 1
φ
3.8 4.8 15
460V / 3
φ
1.9 2.4 15