F1909 (2013 12) Page 1 of 6
BARD MANUFACTURING COMPANY, INC.
WA3S-WA5S Series Air Conditioner
Engineering Specification Guide
1.0 GENERAL
Furnish and install a self-contained, vertical, exterior wall mount,
through-the-wall air conditioner to be manufactured by Bard Manufacturing
Company, Inc. The unit shall be approved and listed by Intertek ETL Listed
(ETL US/C). Unit shall be factory assembled, pre-charged, pre-wired, tested
and ready to operate. Unit performance shall be certified in accordance
with the Air Conditioning and Refrigeration Institute Standard 390-2003 for
Single Package Vertical Units. Unit efficiency shall be specified by EER and
IPLV.
Manufacturers: Capacities shall be as indicated on drawings and units
shall be manufactured by Bard Manufacturing Company, Inc. or prior
approved equal.
2.0 CONSTRUCTION FEATURES
2.1 CABINET
Construction shall be a single, enclosed, weatherproof casing
constructed of 20-gauge galvanized steel. Unit base is constructed
of 16-gauge galvanized steel¹. Each exterior casing panel to be
bonderized and finished with baked-on exterior polyester enamel
paint² prior to assembly. The baked-on cured paint finish shall pass
the industry rub test with a minimum of 72 rubs MEK (Methyl Ethyl
Ketone) or standard rub test of a minimum of 100 rubs using
Tolulene. Cooling section shall be fully insulated with 1-inch
fiberglass to prevent sweating and to muffle sounds. Openings shall
be provided for power connections. Access openings appropriate
for outside structure to all fan motors and compressor for making
repairs and for removing internal components without removing unit
from its permanent installation. Fresh air intake and outdoor coil
shall be protected from intrusions by a sturdy metal grating with less
than 1/4 inch openings.
Colors (Select one)
Beige (standard)
Gray Notes:
Desert Brown ¹ Stainless steel option is 16-ga SS base
Dark Bronze ² Paint finish details do not apply to
Stainless Steel Aluminum or Stainless Steel cabinets
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1

F1909 (2013 12) Page 1 of 6 BARD MANUFACTURING COMPANY, INC. WA3S-WA5S Series Air Conditioner Engineering Specification G

Page 2 -

F1909 (2013 12) Page 2 of 6 Aluminum 2.2 DRAIN PAN Drain pan shall be constructed of 20-gauge stainless steel. 2.3 INSULATION Portions of

Page 3

F1909 (2013 12) Page 3 of 6 2.9 CONTROL CIRCUIT The internal control circuit shall consist of a current limiting 24VAC type 50VA transfo

Page 4 - 4.4 Economizer

F1909 (2013 12) Page 4 of 6 4.3 COMMERCIAL ROOM VENTILATOR OPTIONAL The built-in commercial room ventilator is internally moun

Page 5

F1909 (2013 12) Page 5 of 6 4.5 ENERGY RECOVERY VENTILATOR OPTIONAL The Energy Recovery Ventilator (ERV) shall consist of 2 rotary

Page 6 - 10.0 WARRANTY

F1909 (2013 12) Page 6 of 6 10.0 WARRANTY 10.1 The Bard product specified shall be free from defects in materials and workmanship for a pe