Ventilation System Packages
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the
service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be
introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens
during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts
of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which
restricts any outside air from entering the unit. The blank off plate should be utilized in applications where
outside air is not required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation
air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be
mixed with the conditioned air. The two position damper can be fully opened or closed. The damper blade
is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by
indoor blower operation or can be field connected to be managed based on building occupancy.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet
openings. It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air
quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily
adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor
blower operation or field controlled based on room occupancy. Two versions are available: the CRVS is
power open - spring return on power loss; the CRVP is power open and power return. Complies with
ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”
ECONOMIZER - EIFM OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system
controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer
is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling
requirements without running the compressor. This in turn provides lower operating costs, while extending
the life of the compressor.
Standard Features:
One Piece Construction - Easy to install with no mechanical linkage adjustment required.
Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to
prevent pressurization of tight buildings.
Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.
Proportioning Type Control - for maximum “free cooling” economy and comfort.
Moisture Eliminator & Prefilter - permanent, washable aluminum construction.
Enthalpy Control - adjustable to monitor outdoor temperature and humidity.
Minimum Position Potentiometer - adjustable to control minimum damper blade position for
ventilation purposes.
Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL
The wall-mount energy recovery ventilator is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERVF allows from 200 to
450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior
indoor comfort and humidity levels. In most cases, this can be accomplished without increasing equipment
sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter
conditions.
The ERVF consists of a unique “rotary energy recovery cassette” that provides effective sensible and
latent heat transfer capabilities during summer and winter conditions. Various control schemes are
addressed - including limiting ventilation during building occupancy only.
The ERVF is designed to be internally mounted behind the service door in the W70A or W70L model wall
mount units. It can be built-in at the factory or field installed as an option. ERVF-*5C can be independently
adjusted for intake and exhaust rates.
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.
All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory,
or field-installed at a later date.
Motorized Fresh Air Damper
Barometric Fresh Air Damper
Commercial Room Ventilator
Economizer
Energy Recovery Ventilator
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field
installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air
grille may be required to achieve specified amount of outdoor air intake.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744; 5,002,116.